Distributed Network Protocol for utility SCADA and telemetry
An open SCADA protocol used between master stations, RTUs and IEDs, predominantly in electricity and water utilities, and widely deployed across Australian utility networks.
DNP3 links RTU and PLC outstations to the SCADA master over radio, cellular, fibre or IP WAN. Outstations buffer time-stamped events during a comms loss and report by exception, so control rooms get a complete picture even over slow, unreliable bearers.
Most Australian DNSPs and water utilities specify DNP3 for SCADA telemetry. EEHA Automation designs, configures and commissions DNP3 networks end to end.
Dominant in electricity transmission and distribution and in water and wastewater telemetry. Also used in oil and gas pipelines, rail traction power and large irrigation schemes. Not used in factory automation.
Strongest in North America, Australia and New Zealand, South Africa and parts of South America and Asia. European utilities generally prefer IEC 60870-5-101/104, and IEC 61850 inside substations.
Suitability of DNP3 across the typical integration layers, from field equipment to historian.
Core use: RTU/PLC outstation to SCADA master over radio, cellular, fibre or IP WAN.
Protection relays, reclosers, power quality meters and IEDs report directly to SCADA or via a data concentrator (e.g. SEL RTAC, GE D400).
No native peer-to-peer. Achieved with data concentrators acting as master downstream and outstation upstream.
SCADA normally feeds historians natively or by OPC UA. Inter-control-centre exchange uses ICCP/TASE.2.
Not a sensor or fieldbus protocol. Field instruments connect by hardwired I/O, HART or Modbus.
From Westronic's 1990 design to IEEE 1815 and Secure Authentication, DNP3 has matured into the utility standard it is today.
Base DNP3 has no authentication or encryption: any device that can reach the outstation can issue controls. Secure Authentication (SAv5, IEEE 1815-2012) adds challenge-response authentication of critical requests but not confidentiality; TLS (IEC 62351-3) or VPN tunnels provide encryption. The 2013–14 Project Robus research found roughly 30 implementation flaws in DNP3 masters and outstations, mostly input-validation faults.
| Reference | Year | Affected | Summary |
|---|---|---|---|
| CVE-2013-2788 ICSA-13-252-01 | 2013 | SUBNET Solutions SubSTATION Server | Improper input validation in the DNP3 slave service. Crafted input crashes the service (CVSS v2 7.1). |
| ICSA-13-346-02 | 2013 | Cooper Power Systems Cybectec DNP3 Master OPC Server | Malformed responses cause denial of service on the master. |
| ICSA-14-098-01 | 2014 | OSIsoft PI Interface for DNP3 | Crafted packets can stop the interface, causing a loss of historian data. |
| ICSA-14-329-01 | 2014 | MatrikonOPC for DNP | Unhandled C++ exception from malformed DNP3 traffic crashes the OPC server. |
Representative, not exhaustive. Check CISA ICS advisories, NVD and vendor PSIRTs for the current position.
Aligned with IEC 62443 and the ASD Essential Eight
IP networks: each outstation connects to the master through switches, routers or cellular.
Rings come from RSTP or HSR/PRP (IEC 62439-3) in substations, or from fibre rings.
RS-485 multidrop and radio party-line networks share one channel. Hierarchical chains run through data concentrators.
Native = built into the platform · Native (module/driver) = vendor-supplied add-on · 3rd party = gateway or third-party driver/OPC server.
| Platform | Support | Notes |
|---|---|---|
| Rockwell ControlLogix / CompactLogix | 3rd party | ProSoft in-chassis modules or PLX gateways. |
| Siemens S7-1200 / S7-1500 | Native (comms module) | TeleControl CPs, e.g. CP 1243-8 IRC (S7-1200) and CP 1542SP-1 IRC (ET 200SP). |
| Schneider Modicon M580 / M340 | Native (comms module) | M580 BMENOR2200H RTU module (DNP3 and IEC 60870-5-104). |
| Omron NJ / NX | 3rd party | Protocol gateway. |
| Mitsubishi iQ-R | 3rd party | Protocol gateway. |
| Beckhoff TwinCAT / CODESYS | 3rd party | Third-party libraries or gateway. |
| RTUs / data concentrators | Native | Dedicated RTUs and data concentrators: SCADAPack, SEL RTAC, GE D400. |
| Platform | Support | Notes |
|---|---|---|
| AVEVA Geo SCADA Expert | Native | DNP3 master driver. Core telemetry protocol of the platform. |
| AVEVA Plant SCADA (Citect) | Native (driver) | DNP3 driver available. Confirm the version and licence. |
| Siemens WinCC Unified | 3rd party | No DNP3 runtime channel. Use an OPC UA server (e.g. Kepware, TeleControl Server Basic) or WinCC OA for DNP3-heavy systems. |
| Rockwell FactoryTalk View SE | 3rd party | Via KEPServer Enterprise DNP driver (OPC). |
| Inductive Automation Ignition | Native | DNP3 driver included. |
| RTU platform | Support | Notes |
|---|---|---|
| Schneider SCADAPack 47x / 57x | Native | Outstation (and master for sub-RTUs). Secure Authentication supported. Native pairing with Geo SCADA. |
| Schneider PowerLogic T500 | Native | Schneider's recommended replacement for legacy SAGE RTUs. |
| Ovarro Kingfisher | Native | Widely used in Australian water and utility telemetry. |
| Hitachi Energy RTU500 | Native | Master and slave. Substation and distribution RTU. |
| Siemens SICAM A8000 | Native | Master and slave, serial and TCP/IP. |
| GE Vernova Multilin G500 | Native | Client and server. Substation gateway and data concentrator. |
| SEL RTAC | Native | Client and server, included as standard. |
| Emerson FB3000 / ROC800 | Native | Native DNP3 for oil and gas, pipelines and water telemetry. |
RTU protocol options vary by model, firmware and licence. 'Confirm' means support is not stated in current vendor datasheets; check with the vendor before specifying.
Driver availability changes between releases. Confirm against the current version and licensing before quoting.
In progress through the DNP Users Group, consolidating Technical Bulletins issued since 2012.
Centralised key management, aligned with IEC 62351-5.
Increasingly specified by utilities (IEC 62351-3) alongside or instead of Secure Authentication.
Draft application profile supporting IEEE 1547 requirements for inverters and batteries.
IEC 61850 inside substations, with DNP3 retained for the SCADA link to the control centre.
Security, hardening, testing, migration and troubleshooting: practical answers from EEHA Automation's SCADA and IT/OT team.